Introduction
Flash Mixers and Flocculators the design of flash mix and flocculation chambers.
Both devices operate in much the same way - the water flows through the tank and is mixed in the process.
The primary differences between a flash mix chamber and a flocculation chamber include the detention time and the velocity gradient.
The detention time is the time required for a small amount of water to pass through a tank at a given flow rate.
Mathematically, detention time is given by the following formula:
Formula for detention time.
Where: t = detention time V = tank volume Q = flow
In the case of the flash mix chamber we will consider, the optimal detention time is 30 seconds.
The detention time of a flocculator is much greater, around 30 minutes. The second factor, the velocity gradient, is a measurement of the intensity of mixing in the chamber.
The velocity gradient determines how much the water is agitated in the tank, and also determines how much energy is used to operate the flash mixer or flocculator.
Size and Shape
Although the detention time and velocity gradient are the most important factors influencing the performance of a flash mixer and flocculator, the physical features of each chamber can differ greatly.
The shape of both types of mixers can vary from cylindrical to rectangular or cubical.
The water can be mixed simply by water flowing around baffles, or it can be mixed with a variety of types of paddles, turbines, and propellers.
This page is primarily concerned with determining the volume and dimensions of the tanks.
The volume depends on the amount of water being treated, and is generally much greater for a flocculator than for a flash mix chamber.
The dimensions, in turn, depend on the volume of the tank.
Power Consumption
In addition to calculating the volume and dimensions of various flash mixers and flocculators, we will be determining the amount of power which the devices require to operate.
You can use the power requirements to optimize the efficiency of the flocculators and flash mixers, or merely to predict how much operation of the devices will cost.
Mechanical Rapid Mixer
Specifications
Each set of calculations can only be used on a certain type of device.
This set of calculations is appropriate for a mechanical rapid mixer, a type of flash mix chamber.
A diagram of the flash mixer is shown below.
Diagram of Mechanical Rapid Mixer. Specifications:
Cylindrical tank.
Diameter: 3-10 ft.
Depth: Less than 10 ft.
Four vertical baffles.
Mixing by vertical-shaft, turbine-type impeller.
Flow from bottom to top.
Detention time: 30 sec.
Velocity gradient: 500-1000 sec.-1
A few of these specifications require explanation.
The first few specifications merely limit the physical shape and size of the mixer.
The rest are briefly explained below.
The baffles are flat boards or plates, deflectors, guides, or similar devices placed in flowing water to cause more uniform flow, to absorb energy, and to divert, guide, or agitate liquids.
You can see the baffles as four yellow rectangular shapes around the sides of the flash mixer.
The impeller is shown in white at the center of the chamber.
A motor makes the impeller spin, which in turn agitates the water.
The arrows show the mixing action of the water.
The inlet and outlet devices are not shown in the diagram, but flow should enter from the bottom of the chamber and leave through the top of the chamber.
Summary of Calculations
We will use the following steps to determine the flash mixer's dimensions:
Determine the tank volume.
Assume a depth.
Calculate the tank diameter.
Then we will calculate the power requirements as follows:
Calculate water horsepower.
Calculate electric horsepower.
Estimate power costs.
Tank Volume
The volume of the tank is calculated using the following formula:
V = Q t
Where: V = volume, ft3 Q = flow, cfs t = detention time, sec
You should recognize this formula as a version of the formula we introduced for detention time in a previous section.
The flow for our plant is 2 cfs and the detention time for the mechanical rapid mixer has been specified to be 30 seconds. So the volume of the tank can be calculated as follows:
V = (2 cfs) (30 sec)
V = 60 ft3
Tank Dimensions
In order to determine the dimensions of the tank, we first assume a depth, then we calculate a diameter.
The depth can be anything within the specified range of 10 feet or less. Here, we will assume a depth of 5 feet.
The diameter is calculated as follows:
Formula used to calculate diameter.
Where: D = diameter, ft V = volume, ft3 d = depth, ft
Since we know that the volume of our tank is 60 ft3 from the last section and since we've assumed a depth of 5 feet, the diameter of the tank is calculated as follows:
Calculations.
Power Requirements
The power requirement is the amount of energy which is needed to operate the device.
By calculating the power requirements of the flash mixer, we can determine how much it will cost to run the device.
Calculating the power requirements is done in three steps, as shown below:
1. Calculate water horsepower.
First, we calculate the amount of water horsepower used to operate the flash mixer.
To do so, we use the following formula:
P = mVG2 / 550
Where:
P = water horse power, wHp m = viscosity, lb-sec/ft2 V = volume, ft3 G = velocity gradient, sec-1 550 = conversion factor, ft-lb/sec Hp
The viscosity is the resistance of water to flow due to internal molecular forces.
For water, like many other liquids, the viscosity is related to the liquid's temperature.
The table below shows the viscosity of water at a variety of temperatures.
Water Temperature (°F) Viscosity (lb-sec/ft2) 32 0.0000373 50 0.0000273 60 0.0000233 70 0.0000204 80 0.0000179 85 0.0000169 100 0.0000142 120 0.0000116 140 0.0000098 160 0.0000083 180 0.0000073 212 0.0000058
In this page, we will assume that the water temperature is 60°F, with the corresponding viscosity of 0.0000233 lb-sec/ft.2 You may choose to use other water temperatures in your calculations, especially if your source water temperature varies greatly between summer and winter.
Using a velocity gradient of 750 sec-1, we can calculate the water horsepower used to run our flash mixer as follows:
Calculations
2. Calculate electrical horsepower.
Since motors are not 100% efficient, the amount of electricity used to power the flash mixer is greater than the water horsepower used to mix the water.
We assume a "wire to water" efficiency of 80% and use the following formula to calculate the electrical horsepower:
Formula for calculating electrical horsepower.
Where:
E = electrical horsepower, eHp P = water horsepower, wHp
So, in the case of our example, the electric horsepower would be:
Calculations
E = 1.79 eHp
3. Estimate power costs.
The final step is to estimate the daily cost of the electricity used to run the mechanical rapid mixer.
We will assume that the unit runs 24 hours per day and that the electricity cost is $0.05 per kilowatt-hour.
The following formula can be used to calculate the power cost for the mixer.
Cost = (17.9) (E) (Price)
Where:
17.9 = conversion factor, Kw-hr/eHp-day E = electrical horsepower, eHp Price = electricity price, dollars/Kw-hr
In our example, the cost of running the unit for a day would be:
Cost = (17.9) (1.79) ($0.05)
Cost = $1.60
Conclusions
Our calculations show that our plant can be served by a mechanical rapid mixer with a volume of 60 cubic feet.
With a depth of 5 feet, the mixer's diameter should be 3.9 feet.
It will take a water horsepower of 1.43 to run the device, which translates to an electric horsepower of 1.79.
The flash mixer will cost about $1.60 per day to run. | |
|